Modelling of Transient Ground Potential ‎Rise Due to Vacuum Circuit Breaker ‎Switching in Steel Melting Factories

Document Type : Original Article

Author

Fars regional electric company

Abstract

Circuit-breaker switching and the resulting transients have caused numerous failures in power systems. Among ‎commonly used circuit breakers, the vacuum circuit breaker (VCB) is one of the most widely applied. Because of its ‎advantages in frequent switching operations, VCBs are widely used for switching electric arc furnaces. However, the ‎transients associated with these operations remain a major concern and have been linked to failures in industrial power ‎systems. High-frequency current and voltage transients may occur during VCB energization as a result of prestrike ‎phenomena.‎
This paper presents a detailed switching case study of an arc-furnace VCB (AF-VCB) in a steel-melting plant. The VCB ‎prestrike phenomenon is simulated and analyzed using electromagnetic transient analyses. The simulation model is ‎validated using field measurements. Ground potential rise (GPR) during the switching process is investigated to identify ‎practical methods for reducing switching transients. In addition, practical aspects of physical design and installation are ‎discussed.‎

Keywords

Main Subjects